3" EMT Electrical Conduit
3" EMT Electrical Conduit - is backordered and will ship as soon as it is back in stock.
Cut-length tolerance — ±¼ in. (±0.25 in.)
Applies to every length option, per piece: the cut may be up to ¼ inch shorter or longer than the length ordered. Standard listed lengths may be returned within 14 days after delivery in the same condition as sent. See the return and refund policy.
96-inch orders are intentionally cut to 95¾ inches so the finished package stays within 96 inches. For other standard lengths, we strive for closer cuts, with 99% within ±⅛ inch. Equipment limitations and operator variation mean the full ±¼ in. tolerance still applies.
Need a tighter length tolerance? Contact us before ordering.
Check Transit Time
Estimates. Dispatch timing may affect arrival. Final shipping price at checkout.
Ordering for a project or business?Volume pricing · mixed cut lists · special requirements
Let’s price your project.
Whether you need 100 identical pieces or a full cut list, send us the details. We’ll confirm your price and delivery options before you order.
Couldn't load pickup availability
Key specifications
- Material
- Galvanized steel EMT
- Pipe standard
- UL 797 / ANSI C80.3 source tubing
- Nominal size
- 3 in. EMT trade size
- Wall designation
- EMT — thin-wall electrical tubing
- Outside diameter
- 3.500 in.
- Nominal wall
- 0.072 in.
- Inside diameter (reference)*
- 3.356 in.
- End preparation
- Reamed & chamfered
- Cut-length tolerance
- ±¼ in. (±0.25 in.)
- Pressure / service
- Electrical raceway; not fluid-pressure pipe
- Connections
- Listed EMT connectors and couplings
Reamed & chamfered — less preparation on site
Both cut ends are reamed internally and chamfered externally to remove cutting burrs and sharp edges. Smooth ends help protect conductor insulation during pulling and ease entry into compatible EMT fittings. This reduces repetitive deburring and tool handling when installing multiple short sections.
NEC 358.28(A) calls for cut EMT ends to be reamed or otherwise finished to remove rough edges. Inspect the ends before pulling conductors and ream any new field cuts. Use listed fittings and follow applicable electrical code for the complete installation.
Omega / South Conduit EMT catalog — dimensions and standards
Inside diameter & manufacturing tolerances
*3.356 in. is a manufacturer reference inside diameter. Reference inside diameter is calculated from nominal outside diameter and wall thickness. It is not a guaranteed bore size; actual dimensions vary within manufacturing tolerances. This is not a precision-bore guarantee.
EMT trade size differs from actual OD and ID. Choose listed EMT connectors and couplings by trade size and installation requirements; fittings are not included.
Need an exact inside fit? Contact us before ordering. Do not rely on a reference ID for a close-fitting insert or telescoping assembly.
Technical documentation
3-inch trade-size galvanized steel EMT, cut to the selected length in inches. Both cut ends are reamed and chamfered. Intended for electrical raceway repairs and additions in commercial and industrial buildings.
Technical data
| Material | Galvanized steel electrical metallic tubing (EMT) |
|---|---|
| Trade size | 3 in. (metric designator 78) |
| Nominal outside diameter | 3.500 in. |
| Inside diameter (reference) | 3.356 in. |
| Nominal wall thickness | 0.072 in. |
| Nominal tube weight | 2.63 lb/ft |
| Source tubing standards | UL 797 listed; ANSI C80.3 |
| End preparation | Reamed internally and chamfered externally; unthreaded ends |
| Cut lengths | 4, 6, 12, 18, 24, 36, 48, 60, 72, 84 and 96 inches |
| Cut-length tolerance | ±¼ in. (±0.25 in.) per piece |
| Fitting connection | Listed EMT connectors/couplings for the selected trade size; fittings not included |
| Service | Electrical raceway; not rated for fluid-pressure service |
Reamed and chamfered ends
Internal reaming removes cutting burrs that can scrape conductor insulation during pulling. Exterior chamfering removes sharp cut edges and helps the tube enter compatible EMT fittings. Prepared ends reduce repetitive deburring, tool handling and cleanup at the job site—useful for maintenance teams installing multiple short sections.
Inspect the ends before installation and ream any new field cuts. Install with listed EMT fittings and follow applicable electrical code, including conductor fill, support, bonding and protection for the location. End preparation alone does not establish compliance of the complete installation.
Dimensions and cut tolerance
Trade size is not the measured outside or inside diameter. The 3.356-inch ID is a manufacturer reference value, not a precision-bore guarantee. The reference inside diameter is calculated from nominal outside diameter and wall thickness. Actual dimensions vary within manufacturing tolerances. Confirm any close-fitting insert or telescoping application before ordering.
Lengths are in inches: 48 inches = 4 feet; 96 inches = 8 feet. Each piece may be up to ¼ inch shorter or longer than the ordered cut length. Refunds are not issued solely for length variation within that tolerance. See the store cutting and returns policy for details.
Typical facility applications
Short raceway extensions for lighting circuits, equipment wiring and electrical maintenance in service corridors, mechanical rooms and commercial buildings where EMT is permitted.
Source tubing: Omega Conduit / South Conduit. Manufacturer dimensions and standards · Omega / South Conduit EMT catalog. Image represents the EMT family; use the dimensions above for this trade size.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.